Bristol FIRE PROTECTION SYSTEM CLEAN AGENT SYSTEM ATUM227 (HFC227ea System)

Category
SYSTEM MODEL ATUM227
Design Standard BS EN 15004-1 / NFPA 2001
Extinguishing Agent HFC227ea
Propellant Nitrogen Super-pressurization
Storage Pressure 360psi (25bar) @ 70°F (21°C)
Cylinder Sizes 15L – 180L Welded Cylinders
Cylinder Test Pressure 885psi (61bar)
Cylinder Valve Pressure Differential Piston with Over-pressure Relief Device
Release Devices Manual / Pneumatic / Electric
Release Condition Cross-Zone / Manual

Additional information