Your Cart

Bristol FIRE PROTECTION SYSTEM CLEAN AGENT SYSTEM ATUM227 (HFC227ea System)

Category
SYSTEM MODELATUM227
Design StandardBS EN 15004-1 / NFPA 2001
Extinguishing AgentHFC227ea
PropellantNitrogen Super-pressurization
Storage Pressure360psi (25bar) @ 70°F (21°C)
Cylinder Sizes15L – 180L Welded Cylinders
Cylinder Test Pressure885psi (61bar)
Cylinder ValvePressure Differential Piston with Over-pressure Relief Device
Release DevicesManual / Pneumatic / Electric
Release ConditionCross-Zone / Manual

Additional information

Brand

Request Your Quote