Bristol FIRE DETECTION & ALARM SYSTEMS / ADX ADDRESSABLE Supervised Output Module

MODEL MID-S31
Standard UL 864
Supply Voltage (S-SC) 25.3 ~ 39 VDC
Auxiliary Supply Voltage 24 VDC
Average Current Consumption 154μA (Ty pical) Maximum
Current Consumption on Auxiliary Power Lines Typical 1.15mA
Maximum Output Current 2A @ 2 4 VDC Power Limited
Solenoid Current Consumption Maximum : 443mA
EOL Device 10K ohm s Resistor & 1N5817 Diode
Dimensions 4.2″W x 4.7″H x 1.4″D
Operating Temperature 32°F (0°C) ~ 120°F (49°C)
Mounting 4″ square electrical box
Maximum Output Current 2A@24VDC power limited
Relative Humidity 90% RH Non-Condensing